Performance - Electrical |
| Dielectric Voltage Withstand |
3000 Volts |
| Max. Working Voltage |
600 volts RMS (minimum creepage distance and minimum clearance per UL 840) |
| Circuit Interrupting/Load Breaking |
UL listed and CSA certified for circuit interrupting at full rated current. |
| Temperature Rise |
Max. 30º C temperature rise at full rated current after 50 cycles of overload at 150% rated current at .75-PF |
| Shrouded Contacts |
Complies with California Code Title 8, Art. 51, S2510.7(b) for devices exceeding 300 VAC |
| Horsepower |
Per NEC 430-151 ratings (non-interrupting) |
| Performance - Mechanical |
| Impact Resistance |
Per UL1682 Paragraph 34 |
| Cord Accommodation |
Round portable service cords per UL Std. 62 & CSA C22.2 No. 49. 1 |
| Terminal Identification |
In accordance with UL1682 |
| Cable Pull Out Force |
In accordance with UL1682 |
| Product Identification | Identification label and name per UL 1686 |
| Lockout/Tagout |
Lockout/Tagout hole on 30/50A DuraGard plug complies with OSHA Reg. 29 CFR 1910.147 (V0 30 & 50A plugs only) |
| Performance - Environmental |
| Moisture Resistance |
Per UL1682 Paragraph 49. Watertight/ flap screw cover on receptacle. |
| Flammability | VØ / 5VAper UL94 (DuraV also 5VAin some apps.) |
| Operating Temperatures |